sulfur hexafluoride SF6 Circuit Breaker, Principle, Construction and Working



Sulphur Hexafluoride (SF6) Circuit Breakers

A circuit breaker in which uses sulfur hexafluoride or SF6 gas as arc extinguished medium is known as the SF6 circuit breaker.SF6 is a very good dielectric material which can resist high potentials.SF6 gas is used as the arc quenching medium.Sulfur Hexafluoride (SF6) is an electro-negative gas and has a strong tendency to absorb free electrons. Whenever circuit breaker opens it contacts an arc will form between the two contacts at the same time with high-pressure SF6 gas will be rapidly pumped on the arc.The conducting free electrons in the arc are rapidly captured by the gas to form relatively immobile negative ions.The SF6 circuit breakers are very effective for high power & high voltage operations.

Construction of SF6 Circuit Breakers:-

SF6 circuit breaker consists of fixed and moving contacts enclosed in  arc interruption chamber.which contains SF6 gas.This arc interruption chamber is connected to the SF6 gas reservoir. When the contacts of breaker are opened, the valve mechanism permits a high-pressure SF6 gas from the reservoir to flow towards the arc interruption chamber.
The fixed contact, moving contact are hollow cylindrical arrangements. The moving contact contains rectangular holes in the sides to permit the SF6 gas to let out through these holes after flowing along and across the arc. The tips of fixed contact, moving the contact and arcing horn are coated with the copper-tungsten arc-resistant material. Since SF6 gas is costly, it is recycled & reused by the suitable auxiliary system after each operation of the breaker.
Circuit Breaker

Working of SF6 Circuit Breakers:-

In the initial position of the breaker, the contacts remain surrounded by SF6 gas at a pressure of about 2·8-3.2 kg/cm2. The working of SF6 Circuit Breaker of the first generation was quite simple it is some extent similar to the air blast circuit breaker. Here SF6 gas was compressed and stored in a high-pressure reservoir. During operation of SF6 circuit breaker this highly compressed gas is released through the arc in the breaker and collected to the relatively low-pressure reservoir and then it pumped back to the high-pressure reservoir for re utilize.
The high-pressure flow of SF6 rapidly absorbs the free electrons in the arc path to form immobile negative ions which are ineffective as charge carriers. The result is that the medium between the contacts quickly builds up high dielectric strength and causes the extinction of the arc.After the breaker operation, the valve is closed by the action of a set of springs.

Advantages of SF6 Circuit Breakers:-

Due to the superior arc quenching properties of the SF6 gas, the SF6 circuit breakers have many advantages over oil or air circuit breakers. Some of them are listed below :
(i) Due to the superior arc quenching property of SF6, such circuit breakers have very short arcing time.
(ii) Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much larger currents.
(iii) The SF6 circuit breaker gives noiseless operation due to its closed gas circuit and no exhaust atmosphere, unlike the air blast circuit breaker.
(iv) The closed gas enclosure keeps the interior dry so that there is no moisture problem.
(v) There is no risk of fire in such breakers because SF6 gas is non-inflammable.
(vi) There are no carbon deposits so that tracking and insulation problems are eliminated.
(vii) The SF6 breakers have the low maintenance cost, light foundation requirements, and minimum auxiliary equipment.
(viii) Since SF6 breakers are totally enclosed and sealed from the atmosphere, they are particularly suitable where explosion hazard exists e.g., coal mines.

Disadvantages of SF6 Circuit Breakers:-

(i) SF6 breakers are costly due to the high cost of SF6.
(ii) Since SF6 gas has to be reconditioned after every operation of the breaker, additional equipment is required for this purpose.

Applications of SF6 Circuit Breakers:-

A typical SF6 circuit breaker consists of interrupter units each capable of dealing with currents up to 60 kA and voltages in the range of 50—80 kV. A number of units are connected in series according to the system voltage. SF6 circuit breakers have been developed for voltages 115 kV to 230 kV, power ratings 10 MVA to 20 MVA and interrupting time less than 3 cycles.